AS250D6 specification separates prime 225 kVA / 180 kW from standby 250 kVA / 200 kW at 60 Hz.
A-SH550 table names an SDEC engine and separates Rate Power 500 kVA / 400 kW from Max. Power 550 kVA / 440 kW at 50 Hz.
DB-200GF set data lists 200 kW / 250 kVA at 50 Hz, 400/230 V, with a Deutz BF6M1015-GA engine.
Ask before comparing
Confirm the 50 Hz equivalent rating and the complete-set configuration behind the model sheet.
Ask how the maker defines Rate Power versus Max. Power and which applies to your duty.
Ask whether the published output is a prime or standby rating and request the matching test record.
How this list was made. Selected from the suppliers cited in this article's research, across marketplaces and manufacturer sites — not ranked by quality. Listings are supplier disclosures; no factory visits, product tests or current quotations are claimed. Category illustrations are original concept images. Our research method ↗
/ ArticleSource-led research
At a rated power factor of 0.8, 200 kW equals 250 kVA.
The equation is kW = kVA × power factor. This converts electrical units; it does not make a standby rating suitable for prime operation or determine the generator size required by a site.
How do you convert kW to kVA?
250 kVA = 200 kW ÷ 0.8
Unit conversion only. This does not size a generator, allow for motor starting, or convert standby output into prime output. Use the rated power factor for the actual model.
Why can the same generator have two output ratings?
Generator duty ratings describe different operating conditions. A supplier's published model sheet should identify which rating applies to the offer. Do not apply one universal percentage to convert every maker's standby output into prime output.
Published examples with their original rating labels
Maker-published set data with a Deutz BF6M1015-GA engine; the page does not state a prime or standby designation.
Can you compare a 50 Hz and 60 Hz offer by kW alone?
No. Frequency is part of the specification, and changing speed may change published application ratings. The Cummins G-Drive C-Series page illustrates the distinction for the same engine model. It is engine application data, not a complete generating-set quotation.
Cummins 6CTAA8.3-G7 G-Drive example · manufacturer disclosure
Frequency
Speed
Prime kVA / kW
Standby kVA / kW
50 Hz
1,500 rpm
200 / 160
220 / 176
60 Hz
1,800 rpm
230 / 184
255 / 204
The same source lists this engine application as Non-Regulated. A familiar engine brand or compatible kW figure alone does not establish destination emissions compliance.
Which load and site information still matters?
Supply a load schedule that identifies running demand, starting motors, step loads and sensitive equipment. Record ambient temperature and altitude, and ask the selected maker for its model-specific output and transient-performance confirmation at those conditions. Keep those engineering checks separate from the simple unit calculation above.
RESEARCH IN VIEWElectrical units
REAL POWER200 kW
=
APPARENT POWER250 kVA
×
POWER FACTOR0.8
kW = kVA × power factorIllustrative calculation · PF 0.8
This converts electrical units only. It does not convert standby into prime duty or determine the generator size required by a site. Read the rating qualifications
How should the rating appear on your purchase documents?
Use one line that includes model, rating designation, kW, kVA, power factor, frequency, voltage and phases. Require exceptions to be written into the quotation. Match that line against the offered datasheet and the final acceptance-test record; do not substitute an engine brochure for the complete-set data.
Caterpillar distinguishes backup ratings, prime operation with varying load, and continuous operation with a non-varying load. The paper attaches operating conditions to its categories; the headline output alone does not describe the permitted duty. [4]
Use & limitsThese are Cat’s published categories. They are not a translation table for every maker’s terms.
What to ask next
Editorial checklist
Write expected hours per year and whether the generator is backup or the principal power source.
Provide the expected load profile, including sustained demand and occasional peaks. Ask which published rating definition matches it.
Separate active and apparent demand
Source-based explanation
AGN 087 defines power factor as the relationship between active kWe and apparent kVA. For a buyer brief, retain both quantities and the relevant load condition. [5]
Use & limitsA kW/kVA conversion is arithmetic, not an equipment-sizing result.
What to ask next
Editorial checklist
Ask the engineer or equipment maker to identify the load assumptions and input data used in the sizing calculation.
Separate running PF from starting behavior and flag UPS, drives or other sensitive loads for specific review.
RESEARCH IN VIEWDecision framework
01
Define the brief
Output, duty and site conditions
02
Match the package
Model, components and delivery basis
03
Check the evidence
Entity, documents and test scope
04
Record the gaps
Clarify exceptions before comparing
From a question to a comparable offer. Use the same brief, retain source dates and keep unresolved exceptions visible.
Sources, dates and scope
6 references. Each record keeps its own review date. A manufacturer disclosure is not an independent test; a retrieval date is not a price-effective date. Hover, focus or tap a numbered reference to inspect its source.
Use & limits G-Drive engine application ratings; not a complete generator-set offer.
Named source page / model table; see recorded evidence
Publication date not stated · Original public record · Reviewed 2026-10-19View the recorded evidence
6CTAA8.3-G7: at 50 Hz, prime 200 kVA/160 kW and standby 220 kVA/176 kW; at 60 Hz, prime 230 kVA/184 kW and standby 255 kVA/204 kW. Listed Non-Regulated.